ADM1034
http://onsemi.com
18
Table 17. INTERRUPT STATUS REGISTER 1
(REG. 0X4F)
Bit #
Name
Description
7
LH
1 = Local high temperature limit has been
exceeded.
6
LL
1 = Local low temperature limit has been
exceeded.
5
R1H
1 = Remote 1 high temperature limit has
been exceeded.
4
R1L
1 = Remote 1 low temperature limit has
been exceeded.
3
R1D
1 = Remote 1 diode error; indicates an
open or short on the D1+/D1 pins.
2
R2H
1 = Remote 2 high temperature limit has
been exceeded.
1
R2L
1 = Remote 2 low temperature limit has
been exceeded.
0
R2D
1 = Remote 2 diode error; indicates an
open or short on the D2+/D2 pins.
Table 18. STATUS REGISTER 2 (REG. 0X50)
Bit #
Name
Description
7
LT
1 = Local THERM
 temperature limit has
been exceeded.
6
R1T
1 = Remote 1 THERM
 temperature limit
has been exceeded.
5
R2T
1 = Remote 2 THERM
 temperature limit
has been exceeded.
4
T%
1 = THERM
 % ontime limit has been
exceeded.
3
TA
1 = One of the THERM
 limits has been
exceeded; and the THERM
 output signal
has been asserted.
2
TS
1 = THERM
 state. Indicates the THERM
pin is active; clears on a read if THERM
is not active. Does not generate an
ALERT
 in ALERT
 comp mode.
1
Res
Reserved
0
Res
Reserved
Table 19. STATUS REGISTER 3 (REG. 0X51)
Bit #
Name
Description
7
F1S
1 = Fan 1 has stalled.
6
FA
1 = Fan alarm speed. Fan1 and Fan 2
are running at alarm speed.
5
F2S
1 = Fan 2 has stalled.
4
Res
Reserved
3
Res
Reserved
2
Res
Reserved
1
Res
Reserved
0
ALERT
1 = ALERT
 low; indicates the ALERT
line has been pulled low.
ALERT
 Interrupt Behavior
The ADM1034 generates an ALERT
  whenever an
out-of-limit measurement is made (if it is not masked out).
The user can also detect out-of-limit conditions by polling
the ADM1034 status registers. It is important to note how
the SMBus ALERT
 output behaves when writing interrupt
handler software.
The ALERT
 output on the ADM1034 can be programmed
to operate in either SMBusALERT
 mode or in comp mode.
In SMBusALERT
 mode, the ALERT
 output remains low
until the measurement falls back within its programmed
limits and either the status register is read or an ARA is
completed. In comp mode, the ALERT
 output automatically
resets once the temperature measurement falls back within
the programmed limits.
Configuring the ALERT
 Output
For SMBusALERT
 mode, set the ALERT
 configuration bit
(Bit 3) of the Configuration Register 1 (Address 0x01) to 0.
In SMBusALERT
  mode, a status bit is set when a
measurement goes outside of its programmed limit. If the
corresponding mask bit is not set, the ALERT
 output is
pulled low. If the measured value falls back within the limits,
the ALERT
 output remains low until the corresponding
status register is read or until an ARA is completed (as long
as no other measurement is outside its limits).
For comp mode, set the ALERT
 configuration bit (Bit 3)
of Configuration Register 1 (Address 0x01) to1.
In comp mode, the ALERT
 output is automatically pulled
low when a measurement goes outside its programmed limits.
Once the measurement falls back within its limits (and
assuming no other measurement channel is outside its limits),
the ALERT
 output is automatically pulled high again.
The main difference between the two modes is that the
SMBusALERT
 does not reset without software intervention,
whereas the comp mode ALERT
 output automatically resets.
Figure 30. ALERT
 Comparator and SMBusALERT
Outputs
TEMPERATURE
LIMITS
TIME
CLEARED
ON READ
SMBusALERT
ALERT
 COMP
ALERT
, 705C
Handling SMBusALERT
 Interrupts
To prevent tie-ups due to service interrupts, follow these
steps:
1. Detect an SMBus assertion.
2. Enter the interrupt handler.
相关PDF资料
ADN8810ACPZ-REEL7 IC CURRENT SOURCE(12BIT) 24LFCSP
ADP2140ACPZ3328R7 IC REG DL BCK/LINEAR 10LFCSP
ADP5022ACBZ-6-R7 IC REG TRPL BCK/LINEAR 16WLCSP
ADP5041ACPZ-1-R7 IC REG TRPL BCK/LINEAR 20-LFCSP
ADP5042ACPZ-2-R7 IC REG TRPL BCK/LINEAR 20LFCSP
ADT6402SRJZ-RL7 IC TEMP SENS TRIP PT PP SOT-23-6
ADT6501SRJZP085RL7 IC TEMP SENSOR MICROPWR SOT23-5
ADT7302ARTZ-500RL7 IC SENSOR TEMP 13BIT DGT SOT23-6
相关代理商/技术参数
ADM1034ARQZ-REEL7 功能描述:IC THERM/FAN SPEED CTRLR 16-QSOP RoHS:是 类别:集成电路 (IC) >> PMIC - 热管理 系列:- 标准包装:1 系列:- 功能:温度监控系统(传感器) 传感器类型:内部和外部 感应温度:-40°C ~ 125°C,外部传感器 精确度:±2.5°C 本地(最大值),±5°C 远程(最大值) 拓扑:ADC,比较器,寄存器库 输出类型:2 线 SMBus? 输出警报:无 输出风扇:无 电源电压:2.7 V ~ 5.5 V 工作温度:-40°C ~ 125°C 安装类型:表面贴装 封装/外壳:SOT-23-8 供应商设备封装:SOT-23-8 包装:Digi-Reel® 其它名称:296-22675-6
ADM1040 制造商:AD 制造商全称:Analog Devices 功能描述:Power Supply Monitor ASIC
ADM1041 制造商:AD 制造商全称:Analog Devices 功能描述:Secondary-Side Controller with Current Share and Housekeeping
ADM1041A 制造商:AD 制造商全称:Analog Devices 功能描述:Secondary-Side Controller with Current Share and Housekeeping
ADM1041AARQZ 功能描述:IC SECONDARY SIDE CTRLR 24QSOP RoHS:是 类别:集成电路 (IC) >> PMIC - 电源控制器,监视器 系列:- 产品培训模块:Lead (SnPb) Finish for COTS Obsolescence Mitigation Program 标准包装:2,500 系列:- 应用:多相控制器 输入电压:- 电源电压:9 V ~ 14 V 电流 - 电源:- 工作温度:-40°C ~ 85°C 安装类型:表面贴装 封装/外壳:40-WFQFN 裸露焊盘 供应商设备封装:40-TQFN-EP(5x5) 包装:带卷 (TR)
ADM1041AARQZ-REEL 功能描述:IC SECONDARY SIDE CTRLR 24QSOP RoHS:是 类别:集成电路 (IC) >> PMIC - 电源控制器,监视器 系列:- 产品培训模块:Lead (SnPb) Finish for COTS Obsolescence Mitigation Program 标准包装:2,500 系列:- 应用:多相控制器 输入电压:- 电源电压:9 V ~ 14 V 电流 - 电源:- 工作温度:-40°C ~ 85°C 安装类型:表面贴装 封装/外壳:40-WFQFN 裸露焊盘 供应商设备封装:40-TQFN-EP(5x5) 包装:带卷 (TR)
ADM1041AARQZ-REEL7 功能描述:IC SECONDARY SIDE CTRLR 24QSOP RoHS:是 类别:集成电路 (IC) >> PMIC - 电源控制器,监视器 系列:- 产品培训模块:Lead (SnPb) Finish for COTS Obsolescence Mitigation Program 标准包装:2,500 系列:- 应用:多相控制器 输入电压:- 电源电压:9 V ~ 14 V 电流 - 电源:- 工作温度:-40°C ~ 85°C 安装类型:表面贴装 封装/外壳:40-WFQFN 裸露焊盘 供应商设备封装:40-TQFN-EP(5x5) 包装:带卷 (TR)
ADM1041A-EVALZ 功能描述:BOARD EVAL FOR ADM1041A RoHS:是 类别:编程器,开发系统 >> 评估板 - DC/DC 与 AC/DC(离线)SMPS 系列:- 标准包装:1 系列:- 主要目的:DC/DC,步降 输出及类型:1,非隔离 功率 - 输出:- 输出电压:3.3V 电流 - 输出:3A 输入电压:4.5 V ~ 28 V 稳压器拓扑结构:降压 频率 - 开关:250kHz 板类型:完全填充 已供物品:板 已用 IC / 零件:L7981 其它名称:497-12113STEVAL-ISA094V1-ND